400V SHF
Series(18.5KW~55KW)
|
|
|
Model
|
SHF-18.5K
|
SHF-22K
|
SHF-30K
|
SHF-37K
|
SHF-45K
|
SHF-55K
|
|
Applicable
Motor Capacity
|
18.5kW
|
22kW
|
30kW
|
37kW
|
45kW
|
55kW
|
|
Output
|
Rated
Capacity (*1)
|
26.3kVA
|
31.9kVA
|
42.3kVA
|
51.3kVA
|
62.4kVA
|
76.2kVA
|
|
Rated
Current (*2)
|
38A
|
46A
|
61A
|
74A
|
90A
|
110A
|
|
Overload
Current Rating
|
150%
1 min
|
|
Rated
Output Voltage
|
3Φ,
380V at 50Hz, 400V at 50Hz, 460V at 60Hz
|
|
Input
|
Rated
Voltage and Frequency
|
3Φ,
380V to 460V at 50Hz or 60Hz
|
|
Allowable
Fluctuation
|
Voltage:-15%,
+10% Frequency:±5%
Voltage imbalance: 3%max
|
|
Power
Supply Impedance
|
1%
or more (Use the optional reactor if less than 1%)
|
|
Protective
Structure
|
Totally
enclosed(IP20)
|
|
Cooling
Method
|
Forced
air cooling
|
|
Weight
|
12kg
|
15kg
|
20kg
|
25kg
|
32kg
|
33kg
|
|
Control
Function
|
Control
Method
|
V/f
control or sensorless
vector control
|
|
High-Frequency
Carrier
|
Sine
wave PWM (carrier frequency: 1 to 14 kHz) (*3)
|
|
Output
Frequency
Range
|
0.05
to 600 Hz (starting frequency: 0.05 to 20 Hz
variable) (*4)
|
|
Frequency
Setting Resolution
|
Digital
Setting
|
0.01
Hz (0.05 to 600 Hz)
|
|
Analog
Setting
|
0.1%
(10 bits for 0 to 10 V, 4 to 20 mA),
0.2% (9 bits for 0 to 5 V) for maximum output
frequency
|
|
Frequency
Accuracy
|
Digital
Setting
|
±0.01%
of the output frequency (at -10 to +
40°C
)
|
|
Analog
Setting
|
±0.2%
of the maximum output frequency (at 25 ±
10°C
)
(*5)
|
|
DC
Braking
|
Starting
frequency (0.2 to 20 Hz), operation time (0.1 to
10 s), braking force (1 to 10 steps)
|
|
Additional
Functions
|
Restart
after momentary power failure, flying start,
multi-speed operation, frequency jump, auto alarm
recovery,
PID
control operation, simple scheduled operation,
energy-saving operation, torque limiter (for sensorless
vector control only)
|
|
Operation
Function
|
Start/Stop
Setting
|
Operation
panel, serial communication (RS485, RS
232C
),
control circuit terminals
|
|
Frequency
Command Setting
|
Digital
Setting
|
Operation
panel, serial communication (RS485, RS
232C
),
step setting from terminal board
|
|
Analog
Setting
|
2
channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA,
variable resistor (5 kΩ, 0.3 W or more)
|
|
Input
Signals
|
Frequency
command, forward run command, reverse run command,
acceleration/deceleration time setting, free-run
stop/alarm reset, emergency stop, jogging
selection, step frequency setting, operation
signal hold, torque limiter (sensorless
vector control only)
[Digital
input; 8 channels (arbitrary allocation)] [Analog
input; 1 channel for voltage, 1 channel for
current and voltage]
|
|
Output
Signals
|
Contact
Output
|
Alarm
batch and multifunctional contact output (
1C
contact, 250 VAC,
0.3
A
)
|
|
Monitor
Signal
|
Operating,
frequency matching, overload alarm, undervoltage,
overvoltage, frequency
approach
[Open-collector
output: 3 channels (arbitrary allocation), Analog
output: 2 channels]
|
|
LED
Display
|
Frequency,
output current, synchronous rotation, load factor,
output voltage, pressure, line speed (no units),
operating, alarm
|
|
Serial
Communication I/F
|
RS485,
RS
232C
|
|
Function
Extension
|
Software
upgrade by RS
232C
serial communication supported
|
|
External
Power Supply Output
|
24
VDC, 150 mA (control
terminal)
|
|
Protection
Functions
|
Current
limiting, overcurrent
shutoff, motor overload, external thermal alarm, undervoltage,
overvoltage, momentary
power failure, fin overheat, missing phase
|
|
Warning
Functions
|
Overvoltage
prevention, current limiting during
acceleration/deceleration, brake resistor
overheat, overload, overheating of radiator fins
|
|
Environment
|
Ambient
Temperature
|
-10
to +
50°C
(Remove the top ventilation cover at +
40°C
or higher)
|
|
Storage
Temperature
|
-20
to +
65°C
(*6)
|
|
Ambient
Humidity
|
90%RH
or less (with no condensation)
|
|
Operating
Environment
|
Indoor
at
1,000
m
or lower altitude (No direct sunlight, corrosive
or inflammable gases, oil mist, or dust)
|
| |
|
|
|
|
|
|
|
|
|
|
*1 Rated capacity at the output
voltage of 400 V
*2 Rated current should be reduced according to outout
power when input voltage is 400 VAC or higher.
*3 The maximum carrier frequency varies depending on the
capacity of the inverter and the operating status.
*4 The frequency setting range for sensorless vector
control is 1 to 130 Hz for a four-pole motor (depends on
the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and 20 mA.
*6 This temperature is for short periods, such as during
transportation.
*7 For SHF-37K to SHF-55K, a tap (TAP1 or TAP2) must be
switched according to variable input ranges. Refer to
section 4.2 Terminal Connection Diagrams for details. |
|
|