 Product Module:  ARRAY 4 ~ 24kVA
Santak UPS 

ARRAY is a scalable, modular, flexible solution that combines the highest level of reliability and availability in power protection with the lowest costs of ownership, it is uniquely designed to meet ever-changing commercial & industrial needs and enables users with an expandable level of redundancy through standard hot-swappable UPS-module. ARRAY 4~24kVA, hereinafter called A UPS, is of single phase output and compatible with either three-phase or single phase mains input. A UPS is a scalable power protection system in the range of 4 to 24kVA, this gives you to protect your investment while enabling your system to grow. It becomes easy and simple for future power protection demands by adding UPS-module without further additional costs and space requirements. Thanks to the proven on-line, double conversion with static bypass architecture, each 4kVA UPS-module is a completely independent UPS unit, this design offers the greatest degree of availability in power supply with processed power at all times. Designed with N+X parallel redundancy to provide a fault-tolerant network of power protection for highest system availability, A UPS system provides continuous, high-quality AC power to connected critical equipment, protecting them against any power disturbances due to blackouts, brownouts, surges, spikes, lightning and line noise interference.  

APPLICATION

     Modular, scalable, network-level redundant power protection for multiple servers, mid-size datacenters and business-critical network applications

 KEY FEATURES

Highest flexibility
A UPS is scalable 4 to 24kVA, compatible with either three-phase or single phase mains input. Its modular design gives flexible solution to protect your initial investment in power protection while enabling your system to grow. It becomes easy and convenient to meet your future power demands, simply by adding UPS-module in increments of 4kVA. All modules are hot-swappable, this allows adding or removing modules while the system is running, without any interruption to the output.


N+X redundancy 
This design enables customers with an expendable level of redundancy according to their needs. Users can opt for a greater degree of redundancy with up to N+5, simply by adding UPS-modules into the frame without taking valuable floor space. All UPS-modules are running in parallel, evenly sharing the connected load, not only to maximize redundancy, but also system availability.
   
 

Load

Number of UPS-module

1 unit

2 units

3 units

4 units

5 units

6 units

4KVA

N

N + 1

N + 2

N + 3

N + 4

N + 5

8KVA

 

N

N + 1

N + 2

N + 3

N + 4

12KVA

 

 

N

N + 1

N + 2

N + 3

16KVA

     

N

N + 1

N + 2

20KVA

 

     

N

N + 1

24KVA

 

 

 

 

 

N


   

Highest reliability
With UPS-module containing unique paralleling control, featuring N+X parallel redundancy, A UPS is to provide a fault-tolerant power protection for maximum availability, eliminate downtime and enhance serviceability as well. 

Highest availability
The standard UPS-module is a completely independent UPS unit and adopts the proven double-conversion online technology with static bypass, all modules in the frame are hot-swappable. A UPS provides a perfect power protection against single point-of-failure and ensures maximum uptime and continuous availability. 
 
Highest simplicity
With its modularity, it is easy to install and operate the system which features a user-friendly LCD display and LED indicators on the front panel. Monitoring and control of the UPS system are just at your fingertips, LED indicators provide you with the UPS working status at a glance. 

Highest performance
A UPS with true online double conversion architecture protects against all kinds of common power problems, offers scalable, flexible solution in power protection at the lowest total costs of ownership and higher operating efficiency.
The near to one input power factor reduces the input installation costs, high efficiency that means low heat emission is also good for our environment by using advanced transformer-less high frequency design. 
 
Longer backup time
This unique feature with generator-friendly meets most today’s requirements for long backup time of high-quality AC power supply by either choosing in combination of most generators in the marketplace as a second power source, or installing appropriate number and the capacity of the battery groups specific to users’ needs to realize for long time power protection, users may also opt for an extra Charger module to faster recharge of the large capacity of the battery bank, thereby to maximize availability. 

Manageability
The whole A UPS system can be managed locally and remotely by means of your computer networks from anywhere. 
 
Local management
The system is provided with a 5x20 character backlit LCD display and control panel, it puts all the control and monitoring of the UPS at user’s fingertips.

Remote management
A UPS is provided with two communications paths for remote monitoring, shutdown and management. 

TECHNICAL SPECIFICATIONS

General 

Product

ARRAY,  A UPS

Power Capacity

4 ~ 24kVA / 2.8 ~ 16.8kW

Topology

True online, double-conversion

Construction

Modular (Standard UPS-module of 4kVA)

Redundancy Capability

Network-level N+X redundancy

Bypass

Automatic on overload or UPS failure, manual maintenance switch

Input & output connections

Ha rdwired

Standards

    EMS:  IEC 61000-4-2 Level 4 (ESD)
             IEC 61000-4-3 Level 3 (RS)
             IEC 61000-4-4 Level 4 (EFT)
 
           IEC 61000-4-5 Level 4 (Surge)
    EMI:   IEC62040-2

    Operating Temperature

0 ~ 40 °C

    Relative humidity

20% ~ 90%, non-condensing

Input

Configuration

3-phase (3j4w + G) or single phase (1j2w + G)

Input voltage range

204 ~ 520VAC (3-phase) or 118 ~ 300VAC (single)

Input Frequency

46 ~ 54/56~64 Hz

Input Power Factor

³ 0.98

Output

Configuration

Single phase (1j2w + G)

Nominal Voltage

220VAC

Output Voltage Regulation

±2%

Output Frequency

50/60 Hz

Output Frequency Regulation

±4Hz online, ±0.5% on battery

Output Power Factor

0.7

Overload Capability

110% ~ 130% for 30 sec, >130% for 2 sec

Load Crest Ratio

3:1

Monitoring and Control

LED Indicators

UPS status: Normal , On battery, Bypass, Fault

LCD Display and Controls

5 x 20 character backlit LCD display, Programmable

Communications Port

RS232, RS-485, Intelligent slot

Mechanical

Dimensions of System
      Frame