Thermocouple
unit
-

Features
1. Highly accurate temperature control
Overall accuracy of ±0.8°C (K, J, T range)
enables highly accurate temperature control.
2. Temperature control up to 24 channels
Four and eight channel units are available to make
temperature control up to 24 channels possible.
3. Easy multi-stage temperature control
By combining with PID instruction, temperature
profiling control is realized.
4. Support K, J, T and R thermocouples to
cover all major applications
K and J (-100 to 500°C)
T (-100 to 400°C)
R (0 to 1500°C)
Product type
|
Product name
|
Specifications
|
Product number
|
Part number
|
|
FP0 Thermocouple unit
|
K, J, T, R thermocouple, Resolution: 0.1°C
|
FP0-TC4
|
AFP0420 |
|
K, J, T, R thermocouple, Resolution: 0.1°C
|
FP0-TC8
|
AFP0421 |
Specifications
Input specifications
|
Item
|
Description
|
|
Input points
|
4-channel, 8-channel
(The number of input points can be changed
2, 4, 6 and 8 channels.)
|
|
Input range
|
Thermocouple types K and J
|
-100.0 to 500.0°C/-148.0 to 790.0°F note
1)
|
|
Thermocouple type T
|
-100.0 to 400.0°C/-148.0 to 752.0°F
|
|
Thermocouple type R
|
0.0 to 1500.0°C/32.0 to 1590.0°F note
1)
|
|
Digital output
|
K and J (when using °C): K -1000 to K
5000
K and J (when using °F): K -1480 to K
7900 note 1)
(When range over using °C: K-1001, K5001
or K8000)
(When range over using °F: K-1481, K7901
or K8000)
(When the thermocouple broken: K8000) note
2)
(Until the temperature can be measured at
the initial startup: K8001) note 3)
|
|
T (when using °C): K -1000 to K 4000
T (when using °F): K -1480 to K 7520 note
1)
(When range over using °C: K-1001, K4001
or K8000)
(When range over using °F: K-1481, K7521
or K8000)
(When the thermocouple broken: K8000) note
2)
(Until the temperature can be measured at
the initial startup: K8001) note 3)
|
|
R (when using °C): K 0 to K 15000
T (when using °F): K 320 to K 15900 note
1)
(When range over using °C: K0, K15001 or
K16000)
(When range over using °F: K0, K15901 or
K16000)
(When the thermocouple broken: K16000) note
2)
(Until the temperature can be measured at
the initial startup: K16001) note 3)
|
|
Resolution
|
0.1°C
|
|
Sampling cycle note 5)
|
300 ms: when using 2 channels for an input
points note 4)
500 ms: when using 4 channels for an input
points note 4)
700 ms: when using 6 channels for an input
points note 4)
900 ms: when using 8 channels for an input
points note 4)
|
|
Overall accuracy
|
Range for K and J (-100 to 500°C): ±0.8°C
Range for T (-100 to 400°C): ±0.8°C
Range for R (0 to 99.9°C): ±3°C
(100 to 299.9°C): ±2.5°C
(300 to 1500°C): ±2°C
|
|
Input impedance
|
more than 1 M ohm
|
|
Insulation method
|
- Between thermocouple input terminals and
control unit internal circuits:
Photo-coupler insulation/DC-DC insulation
- Between thermocouple input terminal
channels: PhotoMOS relay insulation
|
|
Input/Output points
|
Input: 32 points note 6)
|
Notes
1) The measurement range available for degree
Celsius is not available for degree Fahrenheit, of which the
upper-limit measurement is set lower than degree Celsius, since
the digital value (temperature value displayed) for degree
Fahrenheit is bigger than that for degree Celsius.
2) When the thermocouple is broken, the digital
value will become K8000 or K16000 within 70 seconds since broken.
Practice in the ladder program a process for avoiding a risk,
would be resulting from a broken thermocouple, and exchange the
thermocouple.
3) Until the conversion data will be ready after
the initial startup was made, the digital value shows K8001 or
K16001. Those are not a temperature data. Create a ladder program,
so that they are not acquired as a temperature data.
4) The settings of the input channel selection
switch.
5) Conversion values for 6-time measurements (6
from the latest 8 measurements, excluding the max. and min.) are
averaged, so that it takes time for the digital value to be
displayed due to the rapid temperature change.
6) The control unit reads the data for 2 channels
per 1 scan by the control unit. Read data by utilizing the sample
program given in the product specifications and manual.
Dimensions
FP0-TC4
-
External dimensions
FP0-TC8
-
External dimensions
|