I/O Link
unit
-

Features
Ideal for cost savings in distributed control
applications
Realizing the distributed control of equipment,
FP0s are placed in strategic locations. While achieving cost
savings, they connect to host PLC (FP2, FP10SH, etc.) with an I/O
link.
Up to 32 stations and maximum 2048 points
connectable to a host PLC.
Product types
|
Product name
|
Specifications
|
Power supply voltage
|
Product number
|
Part number
|
|
FP0 I/O Link unit
|
This is a link unit designed to make the
FP0 function as a station to MEWNET-F (remote I/O system).
|
24V DC
|
FP0-IOL
|
AFP0732 |
|
C-NET adapter S2 type
(for FP0 side)
|
This is an RS485 adapter designed to allow
use of the Computer link function for connecting to a host
computer via C-NET. It comes with a 30 cm FP0 tool port
cable. A power supply is not required.
|
-
|
-
|
AFP15402 |
|
C-NET adapter (RS485)
(for computer side)
|
This is an RS485 adapter designed to allow
use of the Computer link function for connecting to a
network-connected PLC via C-NET from a host computer.
|
100 to 240V AC
|
-
|
AFP8536 |
|
24V DC
|
-
|
AFP8532 |
Specifications
Communication specifications
|
Item
|
Description
|
|
Communication method
|
Two-wire, half duple
|
|
Synchronous method
|
Asynchronous method
|
|
Transmission line
|
2-wire cable (Twisted-pair cable or/VCTF
0.75 mm2× 2C equivalent)
|
|
Transmission distance (Total distance)
|
Max. 700 m 2,296.588
ft.
(using twisted pair cable)
Max. 400 m 1,312.336
ft.
(using VCTF cable)
|
|
Transmission speed (Baud rate)
|
0.5Mbit/s
|
|
Number of control I/O point
per an I/O link unit
|
64 points
(Input: 32 points and Output: 32 points) note)
|
|
Remote I/O map allocation
|
32X/32Y
|
|
Interface
|
Conforming to RS485
|
|
Transmission error check
|
CRC (Cyclic Redumdancy Check) method
|
Note
This point number is the number of points that can
be linked for inputting and outputting via the host PLC and
network MEWNET-F.
If the output for the I/O link unit error flag is
set to ON, this number becomes 63 points (31 input points and 32
output points)
Dimensions
-
External dimensions (unit:
mm)
Note: The installation position for a DIN rail is
in the middle of the unit.
|