S-LINK unit
-

Features
1. Flexible I/O layout is easily possible with
T-type multidrop wiring.
2. An enormous reduction in cabling is
achieved by using 4-wire cable consisting of two signal wires and
two power wires.
3. By using a compact FP0 PLC, further
reductions in control panel size can be achieved.
4. Units are available for FP2/FP2SH and
FP3/FP10SH.
Product Types
|
Product name
|
Specifications
|
Cotrollable I/O points
|
Product number
|
Part number
|
|
FP2 S-LINK unit
|
Direct connection to SUNX Co., Ltd.,
S-LINK reduced-wiring system
CPU unit with 128 points × 1 channel
|
128 points per one unit
|
FP2-SL2
|
AFP2780
|
Configuration
-

Specifications
Transmission Specifications
|
Item
|
S-LINK uit
|
CPU with S-LINK
|
|
Number of channels
|
1
|
2
|
|
Number of I/O points
|
128 points max.
|
128 points ×2 max.
|
|
The number of input and output points can
be selected for each channel , using the switch on the
main unit.
Input: 0/32/64/96/128 points
Output: 0/32/64/96/128 points
(16-point input and 16-point output also
possible)
|
|
Rated power supply voltage
|
+24V DC ±10% / Allowable ripple p-p±10%
max.
(Supplied from IN-24V IN-0V of the S-LINK
terminal block)
|
|
Current consumption note 1)
|
[S-LINK controller current consumption
(including D-G line current consumption)] + 24V DC 1.6A
max.
|
|
[Maximum current which can be supplied
(supplied to S-LINK devices and I/O
devices from 24V - 0V line)] + 24V DC 5A
(fuse: 5A)
|
|
Transmission method
|
Bi-directional time-divided multiple
signal transmission
|
|
Synchronization method
|
Bit synchronization, frame synchronization
|
|
Transmission protocol
|
S-LINK protocol
|
|
Transmission speed
|
28.5kbps
|
|
Transmission distance note 2)
|
128 I/O signals can be transmitted over a
pair of wires up to a distance to 200m max.
(400m when a booster is used)
|
|
FAN-out note 2)
|
320
|
|
Connection method
|
'T'- branch multi-drop wiring or
multi-drop wiring (+24V/0V/D - G line [function
provided to protect again short-circuiting
between D-G line])
|
|
Interface with FP2 CPU note 3)
|
Common memory system
Reading possible through F150 and P150
instruction; writing possible through
F151 and P151 instruction
|
|
Display indicators
|
Transmission indicator
|
Green LED blinks in response to
synchronization signals
|
|
Error indicators
|
Red LED light up depending on the error
|
|
Address display
|
Red 7-segment LED When normal:
If error occurs: Error address display
(hexadecimal) lights
In RUN mode: No. of units connected
flashes when system SET button is turned on
In CHK. mode: Recognized address or
address where error occurred flashes when system SET
button is turned on
|
|
I/O (on/off) indicators
|
Green LED
On/off conditions of S-LINK I/O devices
are displayed in groups of 8 points.
The address to be displayed are selected
by the monitor switch.
|
Notes
1) For detailed information on current
consumption, refer to "Determining the Power Supply
Capacitance" in the S-LINK Design Manual.
2) For information on the booster and FAN - out,
refer to the S-LINK Design Manual.
3) The number of input and output points is
automatically reflected in input X and output Y.
Dimensiond
-

|