Power Supply
Unit
-

Features
1. 4 types selectable depending on the rated
voltage and output capacity.
2. High capacity type is also available for a
lot of modules usage.
Perfect for when there are many intelligent units
and modules.
Product Types
|
Product name
|
Specifications
|
Product number
|
Part number
|
|
FP2 Power supply unit
|
Input: 100 to 120 V AC, Output: 2.5 A
|
FP2-PSA1
|
AFP2631
|
|
Input: 200 to 240 V AC, Output: 2.5 A
|
FP2-PSA2
|
AFP2632
|
|
Input: 100 to 240 V AC, Output: 5 A
|
FP2-PSA3
|
AFP2633
|
|
Input: 24 V DC, Output: 5 A
|
FP2-P5D2
|
AFP2634
|
Specifications
Performance Specifications
|
Item
|
FP2-PSA1
(AFP2631)
|
FP2-PSA2
(AFP2632)
|
FP2-PSA3
(AFP2633)
|
FP2-PSD2
(AFP2634)
|
|
Input
|
Rated voltage
|
100 to 120V AC
|
200 to 240V AC
|
100 to 240V AC
|
24V DC
|
|
Current consumption
|
0.4A or less
(at 100 V AC)
|
0.2A or less
(at 200 V AC)
|
0.7A or less
(at 100 V AC)
0.4A or less
(at 200 V AC)
|
2.5A or less
|
|
Surge current
|
40A or less(55°C 131
° F)
|
30A or less(25°C 77
° F)
|
10A or less
|
|
Rated frequency
|
47Hz to 63Hz
|
|
Operating voltage range
|
85 to 132V AC
|
170 to 264V AC
|
85 to 264V AC
|
20.4 to 31.2V DC note)
|
|
Output
|
Output capacity at 5 V
|
Max. 2.5 A
|
Max. 5 A
|
|
Alarm contact capacity
|
1A 30V DC
|
|
Alarm contact operation
|
When the ALARM LED of CPU unit is lit
|
|
Alarm contact type
|
1c contact
|
|
Leakage current
|
Between input and ground terminals, 0.75
mA or less
|
|
Breakdown voltage
|
1500 V AC for 1 minute (between input and
ground terminals)
|
|
Insulation resistance
|
100M ohm 500V DC (between input and ground
terminals)
|
|
Guaranteed lifetime
|
20000 hours at 55°C 131
° F)
|
|
Overcurrent protection function
|
Built-in o vercurrent protection
|
|
Fuse
|
Built-in type
|
|
Terminal screw
|
M3
|
|
Weight
|
Approx 180g 6.349 oz
|
Approx 180g 6.349 oz
|
Approx 280g 9.876 oz
|
Approx 300g 10.581
oz
|
|
Module size
|
1 module
|
1 module
|
2 module
|
2 module
|
Note)
Allowable voltage fluctuation range after startup
for the FP2-PSD2 is -35% to +30%. At startup, apply -15%
to +30% the rated voltage for 100 ms or more.
Dimensions
FP2-PSA1/FP2-PSA2
-
External dimensions
FP2-PSA3/FP2-PSA4
-
External dimensions

|