Communication
Cassette
-

Features
1. Communications function added to FP SIGMA
to save space.
Since the communication cassette fits inside the
FP SIGMA Control Unit, a communications function can be added
without consuming space on control boards.
2. Type also available with RS232C × 1ch and
RS485 × 1ch.
Distributed control (RS485 data transmission)
using linked PLCs, etc., is possible while using RS232C to
communicate with standalone devices
(for example an Image checker).
Product types
|
Product name
|
Specifications
|
Product number
|
Part number
|
|
FP SIGMA 1-channel, RS232C type
Communication cassette
|
Cassette for control unit installation.
Enables communications with devices with
RS232C interface.
|
FPG-COM1
|
AFPG801
|
|
FP SIGMA 2-channel, RS232C type
Communication cassette
|
Cassette for control unit installation.
Enables communications with devices with
RS232C interface.
|
FPG-COM2
|
AFPG802
|
|
FP SIGMA 1-channel, RS485 type
Communication cassette
|
Cassette for control unit installation.
PLC linking between FP SIGMAs or
communication with devices
with RS485 interface possible or PLC link
between FP SIGMAs.
|
FPG-COM3
|
AFPG803
|
|
FP SIGMA 1-channel, RS232C and
1-channel, RS485 type
Communication cassette
|
Cassette for control unit installation.
Enables communications with devices with
RS232C or RS485 interface.
|
FPG-COM4
|
AFPG806
|
Specifications
Serial communication Specifications (1:1
communication) note 1)
|
Item
|
Description
|
|
Communication method
|
Half duplex
|
|
Synchronous method
|
Asynchronous method
|
|
Transmission line
|
3-core or 5-core shielding cable
|
|
Transmission distance
|
15 m 49.21 ft.
|
|
Transmission speed (Baud rate)
|
2400 bits/s to 115.2 k bits/s
|
|
Interface
|
Conforming to RS232C
(connected via the terminal block)
|
Note 1) In order to use the serial communication
function (1:1 communication), a RS232C type communication cassette
is required.
Serial communication Specifications (1:N
communication) note 1)
|
Item
|
Description
|
|
Communication method
|
Two-wire, half duplex
|
|
Synchronous method
|
Asynchronous method
|
|
Transmission line
|
Shielding twisted-pair cable or VCTF
|
|
Transmission distance
(Total distance)
|
Maximum 1200 m 3937
ft.note 4) 5)
|
|
Transmission speed
(Baud rate)
|
2400 bits/s to 115.2 k bits/s
19200 bits/s when a C-NET adapter is
connected note 2) 4) 5)
|
|
Number of connected
units (stations)
|
Maximum 99 units (stations)
32 units (stations) max. when a C-NET
adapter is
connected note 3) 4) 5)
|
|
Interface
|
Conforming to RS485
(connected via the terminal block)
|
-

Notes 1) In order to use the serial communication
function (1:N communication), a RS485 type communication cassette
is required.
2) The transmission speed (baud rate) and
transmission format are specified using the system registers.
3) Unit (station) numbers are specified using the
system registers. Up to 31 units (stations) can be set, using the
switches on the control unit.
4) When connecting a commercially available device
that has an RS485 interface, please confirm operation using the
actual device. In some cases, the number of units (stations),
transmission distance, and transmission speed (baud rate) vary
depending on the connected device.
5) The values for the transmission distance,
transmission speed (baud rate), and number of units (stations)
should be within the values noted in the graph below.
PLC link function Specifications note 1)
|
Item
|
Description
|
|
Communication method
|
Token bus
|
|
Transmission method
|
Floating master method
|
|
Transmission line
|
Shielding twisted-pair cable or VCTF
|
|
Transmission distance (Total distance)
|
1200 m 3937 ft.
|
|
Transmission speed (Baud rate)
|
115.2 k bits/s
|
|
Number of connected units (stations)
|
Maximum 16 units note 2)
|
|
PLC link capacity
|
Link relay: 1024 points, link register:
128 words
|
|
Interface
|
Conforming to RS485 (connected via the
terminal block)
|
Notes 1) A RS485 type communication cassette is
required in order to use the PLC link function.
2) Unit (station) numbers are specified using the
switches on the control unit or the system registers.
Dimensions
When the communication cassette is used
-
External dimensions
|