Serial
Data Unit
-

Features
1. Data input/output is executed by
Reading can be performed simply by using
high-level instruction F150 (READ), and writing by using
high-level instruction F151 (WRT).
Since the subsequent processing is performed by
the serial data unit through memory shared by the CPU unit, it is
not necessary to work out a complicated program.
2. Free combination of I/O devices
It is possible to use it in three ways: input
only, output only, and input and output
3. 500 bytes of data can be transmitted and
received at a time
4. No limitation on the number of units used
The number of units used is not limited.
This permits the connection of units in number
equivalent to 48 channels per CPU.
5. Can also be used as a C-NET master station.
The FP3/FP10SH can also be used as the data
collection terminal for our C-NET network.
Product Types
|
Product name
|
Specifications
|
Part number
|
|
FP3 Serial Data Unit
|
Serial I/O can be performed by a sequence
instruction.note 1) RS232C × 2 channels
|
AFP3460 |
Notes: 1) Use the accompanying D-SUB connector (9
pins) or a separately sold cable.
Configuration
-

Specifications
Performance Specifications
|
Item
|
Description
|
|
Interface
|
RS232C port
|
|
Transmission speed (Baud rate)
|
300/600/1200/2400/4800/9600/19200 bits/s
|
|
Communication method
|
Half duplex
|
|
Synchronous method
|
Start-stop synchronous method
|
|
Transmission distance
|
Max. 15 m 49.215 ft.
|
|
Transmission format
|
ASCII
|
|
Transmission data format
|
Stop bit
|
1-bit/2-bit
|
|
Parity
|
None/even/odd
|
|
Character bits
|
7-bit/8-bit
|
|
Data transmission order
|
0 bit first in units of characters
|
|
Transmission unit
|
In units of messages to the end terminal
(Length can be changed.)
|
|
Maximum message length
|
Max. 500 bytes/frame
(including end and start codes)
|
|
Terminator (end code) settings
|
Selects among three types of CR, CR and LF
and ETX or
sets the desire code using shared memory
|
|
Header (starting code)
|
Valid/Invalid
|
|
X-ON/Y-OFF control
|
Valid/Invalid
|
|
Other control functions
|
Transmission mode without end code
(using sequence control)
|
|
Other control functions
|
Software reset (using sequence control)
|
|
Weight
|
Approx. 250 g 8.818
oz
|
|